Instrumentation Cable (300 Volt)

HomeIndustrial CableInstrumentation Cable (300 Volt)
Instrumentation Cable (300 Volt) 2017-06-29T16:09:05+00:00

Project Description

XLPE/XL-CPE Instrumentation Cable with Overall Shielded Pairs/Triads

XLPE/XL-CPE Instrumentation Cable with Overall Shielded Pairs/Triads
UL Type PLTC, 300 V

PLTC Cable Approvals:

  • Industry Compliances:
    • UL 13 Type PLTC
    • UL 1581
  • Flame Tests Compliances:
    • UL 1581 VW-1
    • IEEE 383
    • IEEE 1202
    • CSA FT-4
  • Other Compliances
    • EPA 40 CFR, Part 261 for leachable lead content per TCLP
    • OSHA acceptable

PLTC Cable Construction:

  • Conductor:
    • 20 AWG thru 16 AWG tinned, annealed copper per ASTM B33
    • Class B stranding per ASTM B8
  • Insulation:
    • Flame Retardant Cross-linked Polyethylene (XPLE)
    • Color-coded per ICEA Method 1:
    • Pairs: Black and White
    • Triads: Black, White and Red
  • Shield:
    • Overall shield is aluminum/polyester in contact with stranded tinned copper drain wire
  • Jacket:
    • Cross-Linked Chlorinated Polyethylene (XL-CPE)
  • Options:
    • Bare copper conductor
    • Class C Stranding
    • Individual and overall shielded pairs/triads
    • Thermoplastic, Low-Smoke, Zero-Halogen (LSZH) jacket
    • In accordance with UL subject 2250 as Instrumentation Tray Cable (ITC)
    • Other constructions available upon request

PLTC Cable Applications:

  • Typical applications include audio, intercom, control, energy management and alarm circuits.
  • Acceptable for use in free air or raceways in accordance with NEC
  • In ducts, cable trays or conduit
  • Permitted for use in Class 1 Division 2 industrial hazardous locations per NEC
  • In accordance with UL subject 13 as Power-Limited Circuit Cable
  • In class 3 circuits in accordance with NEC
Part NumberAWG SizeConductor StrandingNo. of PairsNo. of TriadsNom. Insul. Thick. (in)Jacket ThickNom. O.D. of Cable (in)Approx LBS/MFT
168885-18207/.01211.012.035.23027
168890-18207/.01211.012.035.24033
168895-18207/.01212.012.040.32048
154830-18207/.01214.012.040.37073
154835-18207/.01218.012.050.500138
154840-18207/.012112.012.050.575186
168900-18207/.012116.012.060.665248
168905-18207/.012120.012.060.740300
154845-18207/.012124.012.060.765350
155820-18207/.012136.012.0701.005525
154850-18207/.012150.012.0701.175697
168910-18187/.01521.015.035.24532
168915-18187/.01521.015.035.25540
168920-18187/.01522.015.040.35058
168925-18187/.01524.015.050.42599
168930-18187/.01528.015.050.545173
168935-18187/.015212.015.060.640245
168940-18187/.015216.015.060.730318
168945-18187/.015220.015.060.810392
168950-18187/.015224.015.070.895450
168955-18187/.015236.015.0701.095672
168960-18187/.015250.015.0701.255904
154760-18167/.01921.015.035.27041
168965-18167/.01921.015.035.28554
168970-18167/.01922.015.050.43085
168975-18167/.01924.015.050.490135
168980-18167/.01928.015.060.650246
168985-18167/.019212.015.060.755346
168990-18167/.019216.015.060.845444
168995-18167/.019220.015.060.900552
169000-18167/.019224.015.0701.020655
169005-18167/.019236.015.0701.225649
169010-18167/.019250.015.0801.4151308
Individual and Overall Shielded Pairs

XLPE/XL-CPE Instrumentation Cable with Individual and Overall Shielded Pairs
UL Type PLTC, 300 V

XLPE/XL-CPE Instrumentation Cable Approvals:

  • Industry Compliances:
    • UL 13 Type PLTC
    • UL 1581
  • Flame Tests Compliances:
    • UL 1581 VW-1
    • IEEE 383
    • IEEE 1202
    • CSA FT-4
  • Other Compliances:
    • EPA 40 CFR, Part 261 for leachable lead content per TCLP
    • OSHA acceptable

XLPE/XL-CPE Instrumentation Cable Construction:

  • Conductor:
    • 20 AWG thru 16 AWG tinned, annealed copper per ASTM B33
    • Class B stranding per ASTM B8
  • Insulation:
    • Flame Retardant Cross-linked Polyethylene (XLPE)
    • Color-coded per ICEA Method 1:
      • Pairs: Black and White
  • Shield:
    • Individual and overall shielded pairs
    • Individual pairs are 100% aluminum/polyester in contact with stranded tinned copper drain wire
    • Overall shield is aluminum/polyester in contact with stranded tinned copper drain wire
  • Jacket:
    • Cross-Linked Chlorinated Polyethylene (XL-CPE)
  • Options:
    • Bare copper conductor
    • Class C Stranding
    • Overall shielded pairs
    • Thermoplastic, Low-Smoke, Zero-Halogen (LSZH) jacket
    • In accordance with UL subject 2250 as Instrumentation Tray Cable (ITC)
    • Other constructions available upon request

XLPE/XL-CPE Instrumentation Cable Applications:

  • Typical applications include audio, intercom, control, energy management and alarm circuits.
  • Acceptable for use in free air or raceways in accordance with NEC
  • Permitted for use in Class 1 Division 2 industrial hazardous locations per NEC
  • In ducts, cable trays or conduit
  • In accordance with UL subject 13 as Power-Limited Circuit Cable
  • In class 3 circuits in accordance with NEC
Part NumberAWG SizeConductor StrandingApprox LBS/MFTNo. of PairsNom. Insul. Thick. (in)Jacket ThickNom. O.D. of Cable (in)
169015-18207/.0121542.012.040.340
154770-18207/.0121934.012.050.415
154775-18207/.01211578.012.050.525
154780-18207/.012123312.012.060.645
169020-18207/.012129416.012.060.715
169025-18207/.012135720.012.060.785
154785-18207/.012142224.012.070.875
154790-18207/.012162036.012.0701.045
169030-18207/.012182850.012.0701.215
169035-18187/.0152762.015.050.415
169040-18187/.01521134.015.050.475
169045-18187/.01522038.015.060.605
169050-18187/.015230012.015.060.750
169055-18187/.015238316.015.060.830
169060-18187/.015248320.015.070.945
169065-18187/.015257124.015.0701.045
169070-18187/.015281636.015.0701.225
169075-18187/.0152111950.015.0801.450
169080-18167/.0192922.015.050.440
169085-18167/.01921634.015.050.545
169090-18167/.01922878.015.060.965
169095-18167/.019243712.015.060.885
169100-18167/.019255316.015.070.980
169105-18167/.019268020.015.0701.080
169110-18167/.019280024.015.0701.235
169115-18167/.0192110836.015.0801.405
169120-18167/.0192152350.015.0801.640

XLPE/PVC Instrumentation Cable with Overall Shielded Pairs/Triads

XLPE/PVC Instrumentation Cable with Overall Shielded Pairs/Triads
UL Type PLTC, 300 V

XLPE/PVC Instrumentation Cable with Overall Shielded Pairs/Triads Approvals:

  • Industry Compliances:
    • UL 13 Type PLTC
    • UL 1581
  • Flame Tests Compliances:
    • UL 1581 VW-1
    • IEEE 383
  • Other Compliances:
    • EPA 40 CFR, Part 261 for leachable lead content per TCLP
    • OSHA acceptable

XLPE/PVC Instrumentation Cable with Overall Shielded Pairs/Triads Construction:

  • Conductor:
    • 18 AWG thru 16 AWG bare, annealed copper per ASTM B3
    • Class B stranding per ASTM B8
  • Insulation:
    • Flame Retardant Cross-linked Polyethylene (XLPE)
    • Color-coded per ICEA Method 1:
      • Pairs: Black and White
      • Triads: Black, White and Red
  • Shield:
    • Overall shielded pairs/triads
    • Overall shield is aluminum/polyester in contact with stranded tinned copper drain wire
  • Jacket:
    • Flame Retardant and sunlight-resistant Polyvinylchloride (PVC)
  • Options:
    • Tinned copper conductor
    • Class C Stranding
    • Individual and overall shielded pairs/triads
    • Ethylene Propylene Rubber (EPR) insulation
    • In accordance with UL subject 2250 as Instrumentation Tray Cable (ITC)
    • Other constructions available upon request

XLPE/PVC Instrumentation Cable with Overall Shielded Pairs/Triads Applications:

  • Acceptable for use in free air or raceways in accordance with NEC
  • Typical applications include audio, intercom, control, energy management and alarm circuits.
  • In ducts, cable trays or conduit
  • In accordance with UL Subject 13 as Power-Limited Circuit Cable
  • In class 3 circuits in accordance with NEC
  • Permitted for use in Class 1 Division 2 industrial hazardous locations per NEC
Part NumberAWG SizeConductor StrandingNo. of PairsNo. of TriadsNom. O.D. of Cable (in)Nom. Insul. Thick. (in)Approx LBS/MFTJacket Thick
183070-18187/.01521.235.01532.035
171465-18187/.015212.50.01540.040
171470-18187/.01522.365.01556.040
171475-18187/.01524.440.01598.050
171480-18187/.01528.550.015175.050
171485-18187/.015212.675.015250.060
171490-18187/.015216.750.015317.060
171495-18187/.015220.785.015392.060
171500-18187/.015224.905.015476.060
171505-18187/.0152361.080.015681.070
171510-18187/.0152501.245.015913.070
183075-18167/.01921.262.01542.035
171515-18167/.01921.280.01553.040
171520-18167/.01922.430.01581.050
171525-18167/.01924.490.015131.050
171530-18167/.01928.650.015254.060
171535-18167/.019212.755.015350.060
171540-18167/.019216.845.015451.060
171545-18167/.019220.880.015545.070
171550-18167/.0192241.020.015657.070
171555-18167/.0192361.220.015965.070
171560-18167/.0192501.405.0151322.080
XLPE/PVC Instrumentation Cable with Individual and Overall Shielded Pairs

XLPE/PVC Instrumentation Cable with Individual and Overall Shielded Pairs
UL Type PLTC, 300 V

XLPE/PVC Instrumentation Cable Approvals:

  • Industry Compliances:
    • UL 13 Type PLTC
    • UL 1581
  • Flame Tests Compliances:
    • UL 1581 VW-1
    • IEEE 383
  • Other Compliances:
    • EPA 40 CFR, Part 261 for leachable lead content per TCLP
    • OSHA acceptable

XLPE/PVC Instrumentation Cable Construction:

  • Conductor:
    • 18 AWG thru 16 AWG bare, annealed copper per ASTM B3
    • Class B stranding per ASTM B8
  • Insulation:
    • Flame retardant Cross-linked Polyethylene (XLPE)
    • Color-coded per ICEA Method 1:
      • Pairs: Black and White
  • Shield:
    • Individual and overall shielded pairs
    • Individual pairs are 100% shielded with Flexfoil aluminum/polyester in contact with stranded tinned copper drain wire
    • Overall shield is aluminum/polyester in contact with stranded tinned copper drain wire
  • Jacket:
    • Flame retardant and sunlight-resistant Polyvinylchloride (PVC)
  • Options:
    • Tinned copper conductor
    • Class C Stranding
    • Overall shielded pairs
    • Ethylene Propylene Rubber (EPR) insulation
    • In accordance with UL subject 2250 as Instrumentation Tray Cable (ITC)
    • Other constructions available upon request

XLPE/PVC Instrumentation Cable Applications:

  • Acceptable for use in free air or raceways in accordance with NEC
  • Typical applications include audio, intercom, control, energy management and alarm circuits.
  • In ducts, cable trays or conduit
  • In accordance with UL Subject 13 as Power-Limited Circuit Cable
  • In class 3 circuits in accordance with NEC
  • Permitted for use in Class 1 Division 2 industrial hazardous locations per NEC
Part NumberAWG SizeConductor StrandingApprox LBS/MFTNo. of PairsNom. Insul. Thick. (in)Jacket ThickNom. O.D. of Cable (in)
171570-18187/.0152732.015.050.410
171575-18187/.01521174.015.050.475
171580-18187/.01522158.015.050.605
171585-18187/.015230812.015.060.750
171590-18187/.015239216.015.060.830
171595-18187/.015249420.015.070.955
171600-18187/.015258324.015.0701.030
171605-18187/.015283036.015.0701.210
171610-18187/.0152114550.015.0801.425
171620-18167/.0152732.015.050.410
171625-18167/.01521604.015.050.530
171630-18167/.01522938.015.060.710
171635-18167/.015242512.015.060.855
171640-18167/.015256316.015.070.955
171645-18167/.015266420.015.0701.055
171650-18167/.015278024.015.0701.160
171655-18167/.0152113736.015.0801.380
171660-18167/.0152151850.015.0801.580
PVC/PVC Instrumentation Cable with Overall Shielded Pairs/Triads

PVC/PVC Instrumentation Cable with Overall Shielded Pairs/Triads
Instrumentation Tray Cable
UL Type PLTC/ITC, 300 V

Type PLTC, ITC Cable Approvals:

  • Industry Compliances:
    • UL 13 Type PLTC/ITC
  • Flame Tests Compliances:
    • IEEE 383 (70,000 BTU/hr)
    • UL Subject 13 (70,000 BTU/hr) for PLTC
    • UL Subject 2250 (70,000 BTU/hr) for ITC
  • Other Compliances:
    • Meets EPA 40 CFR, Part 261 for leachable lead content per TCLP method
    • OSHA acceptable

Type PLTC, ITC Cable Construction:

  • Conductor:
    • 20 AWG thru 16 AWG bare, annealed copper per ASTM B3
    • Class B stranding per ASTM B8
  • Insulation:
    • Polyvinylchloride (PVC)
    • Color-coded per ICEA Method 1:
      • Pairs: Black and White
      • Triads: Black, White and Red
  • Shield:
    • Overall shielded pairs/triads
    • Overall shield is aluminum/polyester in contact with stranded tinned copper drain wire
  • Jacket:
    • Flame retardant and sunlight-resistant Polyvinylchloride (PVC)
  • Options:
    • Tinned copper conductor
    • Class C Stranding
    • Other constructions available upon request

Type PLTC, ITC Cable Applications:

  • Acceptable for use in free air or raceways in accordance with NEC
  • Typical applications include audio, intercom, control, energy management and alarm circuits.
  • In ducts, cable trays or conduit
  • In accordance with UL Subject 13 as Power-Limited Circuit Cable
  • In class 3 circuits in accordance with NEC
  • In accordance with UL Subject 2250 as Instrumentation Tray Cable (ITC)
  • Permitted for use in Class 1 Division 2 industrial hazardous locations per NEC Article 501-4(b) for UL Type PLTC/ITC cables
  • Per NEC Article 727 for Type PLTC/ITC
Part NumberAWG SizeConductor StrandingNo. of PairsNo. of TriadsNom. Insul. Thick. (in)Jacket ThickApprox LBS/MFTNom. O.D. of Cable (in)
162950-18207/.01211.012.04028.220
162955-18207/.01211.012.04034.241
162960-18207/.01212.012.04041.255
162970-18207/.01214.012.04265.321
169810-18207/.01218.012.050104.475
174045-18207/.012112.012.050195.545
167315-18207/.012116.012.050248.605
174050-18207/.012120.012.060309.650
379805-18207/.012124.012.060376.740
169825-18207/.012136.012.060530.850
169830-18207/.012150.012.070713.970
162915-18187/.01521.015.04035.240
162920-18187/.01521.015.04044.264
162925-18187/.01522.015.04255.325
162940-18187/.01524.015.04290.357
174010-18187/.01528.015.060192.646
174015-18187/.015212.015.060293.670
174020-18187/.015216.015.060374.750
169835-18187/.015220.015.060449.780
169840-18187/.015224.015.070564.915
395860-18187/.015236.015.0707871.030
169845-18187/.015250.015.07010591.180
162885-18167/.01921.015.04045.273
162890-18167/.01921.015.04258.297
162895-18167/.01922.015.04274.344
162905-18167/.01924.015.053132.481
169850-18167/.01928.015.060259.726
149415-18167/.019212.015.060408.755
380265-18167/.019216.015.070526.845
169855-18167/.019220.015.070655.905
169860-18167/.019224.015.0708031.030
169865-18167/.019236.015.07011221.165
169870-18167/.019250.015.08015441.355
PVC/PVC Instrumentation Cable with Individual and Overall Shielded Pairs

PVC/PVC Instrumentation Cable with Individual and Overall Shielded Pairs
UL Type PLTC/ITC, 300 V

Instrumentation Tray Cable Approvals:

  • Industry Compliances:
    • UL 13 Type PLTC/ITC
  • Flame Tests Compliances:
    • IEEE 383 (70,000 BTU/hr)
    • UL Subject 13 (70,000 BTU/hr) for PLTC
    • UL Subject 2250 (70,000 BTU/hr) for ITC
  • Other Compliances:
    • Meets EPA 40 CFR, Part 261 for leachable lead content per TCLP method
    • OSHA acceptable

Instrumentation Tray Cable Construction:

  • Conductor:
    • 20 AWG thru 16 AWG bare, annealed copper per ASTM B3
    • Class B stranding per ASTM B8
  • Insulation:
    • Polyvinylchloride (PVC)
    • Color-coded per ICEA Method 1:
      • Pairs: Black and White
  • Shield:
    • Individual and overall shielded pairs
    • Individual pairs are 100% shielded with aluminum/polyester in contact with stranded tinned copper drain wire
    • Overall shield is aluminum/polyester in contact with stranded tinned copper drain wire
  • Jacket:
    • Sunlight-resistant Polyvinylchloride (PVC)
  • Options:
    • Tinned copper conductor
    • Class C Stranding
    • Other constructions available upon request

Instrumentation Tray Cable Applications:

  • Acceptable for use in free air or raceways in accordance with NEC
  • Typical applications include audio, intercom, control, energy management and alarm circuits.
  • In ducts, cable trays or conduit
  • In accordance with UL Subject 13 as Power-Limited Circuit Cable
  • In class 3 circuits in accordance with NEC
  • In accordance with UL Subject 2250 as Instrumentation Tray Cable (ITC)
  • Permitted for use in Class 1 Division 2 industrial hazardous locations per NEC Article 501-4(b) for UL Type PLTC/ITC cables
  • Per NEC Article 727 for Type PLTC/ITC
Part NumberAWG SizeConductor StrandingApprox LBS/MFTNo. of PairsNom. Insul. Thick. (in)Jacket ThickNom. O.D. of Cable (in)
162965-18207/.0121462.012.040.316
162975-18207/.0121764.012.042.325
169875-18207/.01211488.012.050.426
169880-18207/.012122312.012.060.640
174055-18207/.012128016.012.060.705
169885-18207/.012133920.012.060.780
169890-18207/.012139724.012.060.845
174060-18207/.012158636.012.0701.015
170895-18207/.012178650.012.0701.190
162930-18187/.0152612.015.042.296
162945-18187/.01521004.015.042.410
174030-18187/.01522128.015.060.485
174035-18187/.015231512.015.060.760
380210-18187/.015240116.015.060.845
169900-18187/.015250520.015.070.955
169905-18187/.015259624.015.0701.040
169910-18187/.015284636.015.0701.215
169915-18187/.0152116550.015.0801.450
162900-18167/.0192802.015.042.346
162910-18167/.01921514.015.053.506
149440-18167/.01922888.015.060.665
149445-18167/.019243512.015.060.855
379885-18167/.019257516.015.070.970
169920-18167/.019270520.015.0701.080
379890-18167/.019282824.015.0701.165
169925-18167/.0192121536.015.0801.390
169930-18167/.0192167050.015.0901.655
PVC/PVC Instrumentation Cable with Individual and Overall Shielded Triads

PVC/PVC Instrumentation Cable with Individual and Overall Shielded Triads
UL Type PLTC, 300 V

PVC/ PVC Instrumentation Cable with Individual and Overall Shielded Triads Approvals:

  • PVC Instrumentation Cable Industry Compliances:
    • UL 13 Type PLTC/ITC
  • PVC Instrumentation Cable Flame Test Compliances:
    • IEEE 383 (70,000 BTU/hr)
    • UL Subject 13 (70,000 BTU/hr) for PLTC
    • UL Subject 2250 (70,000 BTU/hr) for ITC
  • Other PVC Instrumentation Cable Compliances:
    • Meets EPA 40 CFR, Part 261 for leachable lead content per TCLP method
    • OSHA acceptable

PVC/PVC Instrumentation Cable with Individual and Overall Shielded Triads Construction:

  • Conductor:
    • 20 AWG thru 16 AWG bare, annealed copper per ASTM B3
    • Class B stranding per ASTM B8
  • Insulation:
    • Polyvinylchloride (PVC)
    • Color-coded per ICEA Method 1:
      • Pairs: Black and White
      • Triads: Black, White and Red
  • Shield:
    • Individual and overall shielded triads
    • Individual triads are 100% shielded with aluminum/polyester in contact with stranded tinned copper drain wire
    • Overall shield is aluminum/polyester in contact with stranded tinned copper drain wire
  • Jacket:
    • Sunlight-resistant Polyvinylchloride (PVC)
  • PVC Instrumentation Cable Options:
    • Tinned copper conductor
    • Class C Stranding
    • Other constructions for PVC Instrumentation Cable available upon request

PVC/PVC Instrumentation Cable with Individual and Overall Shielded Triads Applications:

  • PVC Instrumentation cable is acceptable for use in free air or raceways in accordance with NEC
  • Typical applications for PVC Instrumentation Cable include audio, intercom, control, energy management and alarm circuits.
  • In ducts, cable trays or conduit
  • In accordance with UL Subject 13 as Power-Limited Circuit Cable
  • In class 3 circuits in accordance with NEC
  • In accordance with UL subject 2250 as Instrumentation Tray Cable (ITC)
  • Permitted for use in Class 1 Division 2 industrial hazardous locations per NEC Article 501-4(b) for UL Type PLTC/ITC cables
  • Per NEC Article 727 for Type PLTC/ITC
Part NumberAWG SizeConductor StrandingApprox LBS/MFTNo. of TriadsNom. O.D. of Cable (in)Nom. Insul. Thick. (in)Jacket Thick
169935-18207/.0121592.340.012.040
169940-18207/.0121974.365.012.040
169945-18207/.01211878.566.012.050
169950-18207/.012128712.705.012.060
169955-18207/.012136516.780.012.060
169960-18207/.012144020.860.012.060
169965-18207/.012154124.955.012.070
169970-18207/.0121767361.115.012.070
162935-18187/.0152772.321.015.040
169980-18187/.01521434.444.015.050
174005-18187/.01523758.786.015.060
380150-18187/.015241212.840.015.060
169990-18187/.015255016.960.015.070
169995-18187/.0152668201.060.015.070
170000-18187/.0152785241.145.015.070
170005-18187/.01521151361.365.015.080
170010-18167/.01921042.367.015.040
170015-18167/.01921954.502.015.050
170020-18167/.01923758.786.015.060
170025-18167/.019259712.970.015.070
170030-18167/.0192765161.075.015.070
170035-18167/.0192933201.195.015.070
170040-18167/.01921125241.310.015.080
170045-18167/.01921620361.540.015.080