Project Description

XHHW Tray Cable (XLP/PVC)
-40°C to 90°C Control Cable
Type XHHW-2 Conductors
XHHW Tray Cable (XLP/PVC) Construction:
- Conductor: 18 AWG – 10 AWG Class B Stranded Bare Copper (per ASTM B-3 and B-8)
- Insulation: Flame-Retardant Cross-Linked Polyethylene (XLP)
- Jacket: Black sunlight and moisture resistant Polyvinyl Chloride (PVC)
XHHW Tray Cable (XLP/PVC) Features:
- Rated 90°C wet or dry
- Sunlight and weather resistant
- Excellent abrasion and chemical resistance
- Oil resistant I jacket
XHHW Tray Cable (XLP/PVC) Applications:
- Constructions of 3 or more conductors are permitted by NEC for TC-ER (exposed run)
- Approved for Class I Division 2 hazardous locations per NEC Article 501 (TC)
- Designed for use in conduit, cable tray or direct burial
- Applications include control, power lighting and telemetering where a heat and electrically stable insulation is required
- NEC Article 336 applications
XHHW Tray Cable (XLP/PVC) Approvals:
- UL 1277 Type TC-ER, UL 1685, UL 44 XHHW-2 rated
- ICEA S-95-658 (NEMA WC70)
- Passes IEEE 383 Flame Test (70,000 btu)
- EPA 40 CFR, Part 261, Subpart C, heavy metals per Table 1, TCLP method
Part Number | AWG Size | No. of Cond. | Conductor Stranding | Nom. Insul. Thick. (in) | Jacket Thick | Nom. O.D. of Cable (in) | Approx LBS/MFT |
XLP/PVC 18-2C-FL | 18 | 2 | 7/.0152 | 0.03 | 0.045 | 0.202 x 0.308 | 40 |
XLP/PVC 18-2C | 18 | 2 | 7/.0152 | 0.03 | 0.045 | 0.31 | 44 |
XLP/PVC 18-3C | 18 | 3 | 7/.0152 | 0.03 | 0.045 | 0.327 | 55 |
XLP/PVC 18-4C | 18 | 4 | 7/.0152 | 0.03 | 0.045 | 0.355 | 67 |
XLP/PVC 18-5C | 18 | 5 | 7/.0152 | 0.03 | 0.045 | 0.386 | 80 |
XLP/PVC 18-7C | 18 | 7 | 7/.0152 | 0.03 | 0.045 | 0.418 | 103 |
XLP/PVC 18-9C | 18 | 9 | 7/.0152 | 0.03 | 0.045 | 0.485 | 129 |
XLP/PVC 18-12C | 18 | 12 | 7/.0152 | 0.03 | 0.045 | 0.542 | 180 |
XLP/PVC 18-15C | 18 | 15 | 7/.0152 | 0.03 | 0.06 | 0.632 | 217 |
XLP/PVC 18-19C | 18 | 19 | 7/.0152 | 0.03 | 0.06 | 0.664 | 261 |
XLP/PVC 16-2C-FL | 16 | 2 | 7/.0192 | 0.03 | 0.045 | 0.214 x 0.334 | 53 |
XLP/PVC 16-2C | 16 | 2 | 7/.0192 | 0.03 | 0.045 | 0.334 | 53 |
XLP/PVC 16-3C | 16 | 3 | 7/.0192 | 0.03 | 0.045 | 0.353 | 68 |
XLP/PVC 16-4C | 16 | 4 | 7/.0192 | 0.03 | 0.045 | 0.384 | 85 |
XLP/PVC 16-5C | 16 | 5 | 7/.0192 | 0.03 | 0.045 | 0.418 | 101 |
XLP/PVC 16-7C | 16 | 7 | 7/.0192 | 0.03 | 0.045 | 0.454 | 133 |
XLP/PVC 16-9C | 16 | 9 | 7/.0192 | 0.03 | 0.06 | 0.558 | 183 |
XLP/PVC 16-12C | 16 | 12 | 7/.0192 | 0.03 | 0.06 | 0.622 | 231 |
XLP/PVC 16-15C | 16 | 15 | 7/.0192 | 0.03 | 0.06 | 0.688 | 280 |
XLP/PVC 16-19C | 16 | 19 | 7/.0192 | 0.03 | 0.06 | 0.724 | 339 |
XLP/PVC 16-25C | 16 | 25 | 7/.0192 | 0.03 | 0.08 | 0.884 | 469 |
XLP/PVC 16-30C | 16 | 30 | 7/.0192 | 0.03 | 0.08 | 0.933 | 545 |
XLP/PVC 16-37C | 16 | 37 | 7/.0192 | 0.03 | 0.08 | 1.004 | 819 |
XLP/PVC 14-2C-FL | 14 | 2 | 7/.0242 | 0.03 | 0.045 | 0.228 x 0.362 | 82 |
XLP/PVC 14-2C | 14 | 2 | 7/.0242 | 0.03 | 0.045 | 0.362 | 73 |
XLP/PVC 14-3C | 14 | 3 | 7/.0242 | 0.03 | 0.045 | 0.383 | 95 |
XLP/PVC 14-4C | 14 | 4 | 7/.0242 | 0.03 | 0.045 | 0.418 | 118 |
XLP/PVC 14-5C | 14 | 5 | 7/.0242 | 0.03 | 0.045 | 0.456 | 141 |
XLP/PVC 14-7C | 14 | 7 | 7/.0242 | 0.03 | 0.045 | 0.496 | 187 |
XLP/PVC 14-9C | 14 | 9 | 7/.0242 | 0.03 | 0.06 | 0.609 | 256 |
XLP/PVC 14-12C | 14 | 12 | 7/.0242 | 0.03 | 0.06 | 0.68 | 325 |
XLP/PVC 14-15C | 14 | 15 | 7/.0242 | 0.03 | 0.06 | 0.754 | 395 |
XLP/PVC 14-19C | 14 | 19 | 7/.0242 | 0.03 | 0.06 | 0.794 | 479 |
XLP/PVC 14-25C | 14 | 25 | 7/.0242 | 0.03 | 0.08 | 0.968 | 660 |
XLP/PVC 14-30C | 14 | 30 | 7/.0242 | 0.03 | 0.08 | 0.983 | 769 |
XLP/PVC 14-37C | 14 | 37 | 7/.0242 | 0.03 | 0.08 | 1.102 | 1342 |
XLP/PVC 12-2C-FL | 12 | 2 | 7/.0305 | 0.03 | 0.045 | 0.248 x 0.402 | 90 |
XLP/PVC 12-2C | 12 | 2 | 7/.0305 | 0.03 | 0.045 | 0.402 | 90 |
XLP/PVC 12-3C | 12 | 3 | 7/.0305 | 0.03 | 0.045 | 0.427 | 121 |
XLP/PVC 12-5C | 12 | 5 | 7/.0305 | 0.03 | 0.045 | 0.51 | 173 |
XLP/PVC 12-7C | 12 | 7 | 7/.0305 | 0.03 | 0.045 | 0.556 | 200 |
XLP/PVC 12-9C | 12 | 9 | 7/.0305 | 0.03 | 0.06 | 0.681 | 267 |
XLP/PVC 12-12C | 12 | 12 | 7/.0305 | 0.03 | 0.06 | 0.763 | 336 |
XLP/PVC 12-15C | 12 | 15 | 7/.0305 | 0.03 | 0.06 | 0.848 | 433 |
XLP/PVC 12-19C | 12 | 19 | 7/.0305 | 0.03 | 0.08 | 0.938 | 564 |
XLP/PVC 12-25C | 12 | 25 | 7/.0305 | 0.03 | 0.08 | 1.092 | 691 |
XLP/PVC 12-30C | 12 | 30 | 7/.0305 | 0.03 | 0.08 | 1.155 | 1046 |
XLP/PVC 12-37C | 12 | 37 | 7/.0305 | 0.03 | 0.08 | 1.246 | 1610 |
XLP/PVC 10-2C-FL | 10 | 2 | 7/.0385 | 0.03 | 0.045 | 0.271 x 0.448 | 120 |
XLP/PVC 10-2C | 10 | 2 | 7/.0385 | 0.03 | 0.045 | 0.448 | 120 |
XLP/PVC 10-3C | 10 | 3 | 7/.0385 | 0.03 | 0.045 | 0.476 | 165 |
XLP/PVC 10-5C | 10 | 5 | 7/.0385 | 0.03 | 0.06 | 0.602 | 273 |
XLP/PVC 10-7C | 10 | 7 | 7/.0385 | 0.03 | 0.06 | 0.655 | 369 |
XLP/PVC 10-9C | 10 | 9 | 7/.0385 | 0.03 | 0.06 | 0.765 | 467 |
XLP/PVC 10-12C | 10 | 12 | 7/.0385 | 0.03 | 0.08 | 0.899 | 639 |
XHHW Tray Cable (XLP/PVC)
-40°C to 90°C Control Cable
Type XHHW-2 Conductors
XHHW Tray Cable (XLP/PVC) Construction:
- Conductor: 18 AWG – 16 AWG Class B Stranded Bare Copper (per ASTM B-3 and B-8)
- Insulation: Flame-Retardant Cross-Linked Polyethylene (XLP)
- Jacket: Black sunlight and moisture resistant Polyvinyl Chloride (PVC)
- Shield: 100% coverage, aluminum/polyester foil shield
XHHW Tray Cable (XLP/PVC) Features:
- Rated 90°C wet or dry
- Sunlight and weather resistant
- Excellent abrasion and chemical resistance
- Oil resistant I jacket
XHHW Tray Cable (XLP/PVC) Applications:
- Constructions of 3 or more conductors are permitted by NEC for TC-ER (exposed run)
- Approved for Class I Division 2 hazardous locations
- Designed for use in conduit, cable tray or direct burial
- Ideal for use in control, power lighting and telemetering applications where a heat and electrically stable insulation is required
XHHW Tray Cable (XLP/PVC) Approvals:
- UL 1277 Type TC-ER, UL 1685 and UL 44 XHHW-2 rated
- ICEA S-95-658 (NEMA WC70)
- Passes IEEE 383 Flame Test (70,000 btu)
- EPA 40 CFR, Part 261, Subpart C, heavy metals per Table 1, TCLP method
Part Number | AWG Size | No. of Cond. | Conductor Stranding | Nom. Insul. Thick. (in) | Jacket Thick | Nom. O.D. of Cable (in) |
XLP/PVC 18-2C-S | 18 | 2 | 7/.0152 | 0.03 | 0.045 | 0.314 |
XLP/PVC 18-3C-S | 18 | 3 | 7/.0152 | 0.03 | 0.045 | 0.331 |
XLP/PVC 18-4C-S | 18 | 4 | 7/.0152 | 0.03 | 0.045 | 0.359 |
XLP/PVC 18-5C-S | 18 | 5 | 7/.0152 | 0.03 | 0.045 | 0.39 |
XLP/PVC 18-7C-S | 18 | 7 | 7/.0152 | 0.03 | 0.045 | 0.422 |
XLP/PVC 18-9C-S | 18 | 9 | 7/.0152 | 0.03 | 0.045 | 0.489 |
XLP/PVC 18-12C-S | 18 | 12 | 7/.0152 | 0.03 | 0.045 | 0.546 |
XLP/PVC 16-2C-S | 16 | 2 | 7/.0192 | 0.03 | 0.045 | 0.338 |
XLP/PVC 16-3C-S | 16 | 3 | 7/.0192 | 0.03 | 0.045 | 0.357 |
XLP/PVC 16-4C-S | 16 | 4 | 7/.0192 | 0.03 | 0.045 | 0.388 |
XLP/PVC 16-5C-S | 16 | 5 | 7/.0192 | 0.03 | 0.045 | 0.422 |
XLP/PVC 16-7C-S | 16 | 7 | 7/.0192 | 0.03 | 0.045 | 0.458 |
XLP/PVC 16-9C-S | 16 | 9 | 7/.0192 | 0.03 | 0.06 | 0.562 |
XLP/PVC 16-12C-S | 16 | 12 | 7/.0192 | 0.03 | 0.06 | 0.626 |
XLP/PVC 14-2C-S | 14 | 2 | 7/.0242 | 0.03 | 0.045 | 0.366 |
XLP/PVC 14-3C-S | 14 | 3 | 7/.0242 | 0.03 | 0.045 | 0.387 |
XLP/PVC 14-4C-S | 14 | 4 | 7/.0242 | 0.03 | 0.045 | 0.422 |
XLP/PVC 14-5C-S | 14 | 5 | 7/.0242 | 0.03 | 0.045 | 0.46 |
XLP/PVC 14-7C-S | 14 | 7 | 7/.0242 | 0.03 | 0.045 | 0.5 |
XLP/PVC 14-12C-S | 14 | 12 | 7/.0242 | 0.03 | 0.06 | 0.684 |
XLP/PVC 12-2C-S | 12 | 2 | 7/.0305 | 0.03 | 0.045 | 0.406 |
XLP/PVC 12-3C-S | 12 | 3 | 7/.0305 | 0.03 | 0.045 | 0.431 |
XLP/PVC 12-4C-S | 12 | 4 | 7/.0305 | 0.03 | 0.045 | 0.471 |
XLP/PVC 12-5C-S | 12 | 5 | 7/.0305 | 0.03 | 0.045 | 0.514 |
XLP/PVC 12-7C-S | 12 | 7 | 7/.0305 | 0.03 | 0.06 | 0.59 |
XLP/PVC 12-12C-S | 12 | 12 | 7/.0305 | 0.03 | 0.06 | 0.767 |
XLP/PVC 10-2C-S | 10 | 2 | 7/.0385 | 0.03 | 0.045 | 0.452 |
XLP/PVC 10-3C-S | 10 | 3 | 7/.0385 | 0.03 | 0.045 | 0.48 |
XLP/PVC 10-4C-S | 10 | 4 | 7/.0385 | 0.03 | 0.06 | 0.556 |
XLP/PVC 10-5C-S | 10 | 5 | 7/.0385 | 0.03 | 0.06 | 0.606 |
XLP/PVC 10-7C-S | 10 | 7 | 7/.0385 | 0.03 | 0.06 | 0.659 |
Grounded XHHW Tray Cable (XLP/PVC)
-40°C to 90°C Power Cable
Type XHHW-2 Conductors
Grounded XHHW Tray Cable (XLP/PVC) Construction:
- Conductor: 8 AWG – 1 AWG Class B Stranded Bare Copper (per ASTM B-33 and B-8)
- Insulation: Flame-Retardant Cross-Linked Polyethylene (XLP)
- Jacket: Black sunlight and moisture resistant Polyvinyl Chloride (PVC)
Grounded XHHW Tray Cable (XLP/PVC) Features:
- Rated 90°C wet or dry
- Sunlight and weather resistant
- Excellent abrasion and chemical resistance
- Oil resistant I jacket
Grounded XHHW Tray Cable (XLP/PVC) Applications:
- Constructions of 3 or more conductors are permitted by NEC for TC-ER (exposed run)
- Approved for Class 1 Division 2 hazardous locations per NEC Article 501 (TC)
- Designed for use in conduit, cable tray or direct burial
- Suitable for use in control, power lighting and telemetering applications where a heat and electrically stable insulation is required
- NEC Article 336 applications
Grounded XHHW Tray Cable (XLP/PVC) Approvals:
- UL 1277 Type TC-ER, UL 1685, and UL 44 XHHW-2 rated
- ICEA S-95-658 (NEMA WC70)
- Passes IEEE 383 flame test (70,000 btu)
- EPA 40 CFR, Part 261, Subpart C, heavy metals per Table 1, TCLP method
Part Number | AWG Size | No. of Cond. | Conductor Stranding | Ground AWG Size | Nom. Insul. Thick. (in) | Jacket Thick | Nom. O.D. of Cable (in) | Approx LBS/MFT |
XLP/PVC 8-3C-G | 8 | 3 | 7/.0486 | 10 | 0.03 | 0.06 | 0.603 | 292 |
XLP/PVC 8-4C-G | 8 | 4 | 7/.0486 | 10 | 0.03 | 0.06 | 0.664 | 364 |
XLP/PVC 6-3C-G | 6 | 3 | 7/.0612 | 8 | 0.03 | 0.06 | 0.681 | 424 |
XLP/PVC 6-4C-G | 6 | 4 | 7/.0612 | 8 | 0.03 | 0.06 | 0.748 | 532 |
XLP/PVC 4-3C-G | 4 | 3 | 7/.0772 | 8 | 0.04 | 0.08 | 0.877 | 658 |
XLP/PVC 4-4C-G | 4 | 4 | 7/.0772 | 8 | 0.04 | 0.08 | 0.962 | 831 |
XLP/PVC 2-3C-G | 2 | 3 | 7/.0974 | 6 | 0.04 | 0.08 | 1 | 967 |
XLP/PVC 2-4C-G | 2 | 4 | 7/.0974 | 6 | 0.04 | 0.08 | 1.107 | 1228 |
XLP/PVC 1-3C-G | 1 | 3 | 19/.0664 | 6 | 0.06 | 0.085 | 1.144 | 1216 |
XLP/PVC 1-4C-G | 1 | 4 | 19/.0664 | 6 | 0.06 | 0.085 | 1.261 | 1554 |
XLP/PVC 1/0-3C-G | 1/0 | 3 | 19/.0745 | 6 | 0.06 | 0.085 | 1.23 | 1430 |
XLP/PVC 1/0-4C-G | 1/0 | 4 | 19/.0745 | 6 | 0.06 | 0.085 | 1.331 | 1832 |
XLP/PVC 2/0-3C-G | 2/0 | 3 | 19/.0837 | 6 | 0.06 | 0.085 | 1.336 | 1729 |
XLP/PVC 2/0-4C-G | 2/0 | 4 | 19/.0837 | 6 | 0.06 | 0.085 | 1.476 | 2230 |
XLP/PVC 3/0-3C-G | 3/0 | 3 | 19/.0940 | 4 | 0.06 | 0.085 | 1.442 | 2144 |
XLP/PVC 4/0-3C-G | 4/0 | 3 | 19/.1055 | 4 | 0.06 | 0.085 | 1.74 | 3403 |
XLP/PVC 4/0-4C-G | 4/0 | 4 | 19/.1055 | 4 | 0.06 | 0.085 | 1.808 | 3976 |
XLP/PVC 250-3C-G | 250 | 3 | 37/.0822 | 4 | 0.07 | 0.12 | 1.857 | 3014 |
XLP/PVC 250-4C-G | 250 | 4 | 37/.0822 | 4 | 0.07 | 0.12 | 1.615 | 4038 |
XLP/PVC 350-3C-G | 350 | 3 | 37/.0974 | 3 | 0.07 | 0.12 | 2.222 | 4254 |
XLP/PVC 350-4C-G | 350 | 4 | 37/.0974 | 3 | 0.07 | 0.12 | 2.009 | 5519 |
XLP/PVC 500-3C-G | 500 | 3 | 37/.1162 | 2 | 0.07 | 0.12 | 2.294 | 5846 |
XLP/PVC 500-4C-G | 500 | 4 | 37/.1162 | 2 | 0.07 | 0.12 | 2.541 | 7612 |
POS Tray Cable (XLP/PVC)
-40°C to 90°C Instrumentation Cable
POS Tray Cable (XLP/PVC) Construction:
- Conductor: 18 AWG – 16 AWG Class B Stranded Bare Copper (per ASTM B-33 and B-8)
- Insulation: Flame-Retardant Cross-Linked Polyethylene (XLP)
- Color Code: Black/White; Alpha/numeric print
- Jacket: Black sunlight and moisture resistant Polyvinyl Chloride (PVC)
- Shield: Overall 100% coverage, aluminum/polyester foil shield
POS Tray Cable (XLP/PVC) Features:
- Rated 90°C wet or dry
- Sunlight and weather resistant
- Superior low temperature cold bend characteristics
- Excellent abrasion and chemical resistance
- Flame resistant jacket burns to ash and limited thermoplastic drip
POS Tray Cable (XLP/PVC) Applications:
- Approved for Class 1 Division 2 hazardous locations per NEC Article 501 (TC)
- Designed for use in conduit, cable tray or direct burial
- Suitable for use in industrial and utility applications where reliability and performance are paramount
- NEC Article 336 applications
POS Tray Cable (XLP/PVC) Approvals:
- UL 1277 Type TC, UL 1581, and UL 1685 approved
- ICEA S-73-532 and ICEA S-95-658 rated
- Passes IEEE 383 Flame Test (70,000 btu)
- EPA 40 CFR, Part 261, Subpart C, heavy metals per Table 1, TCLP method
Part Number | AWG Size | No. of Pairs | Conductor Stranding | Nom. Insul. Thick. (in) | Jacket Thick | Nom. O.D. of Cable (in) | Approx LBS/MFT |
XLP/PVC 18-1P-S | 18 | 1 | 7/.0152 | 0.03 | 0.045 | 0.314 | 45 |
XLP/PVC 18-2P-S | 18 | 2 | 7/.0152 | 0.03 | 0.045 | 0.476 | 89 |
XLP/PVC 18-4P-S | 18 | 4 | 7/.0152 | 0.03 | 0.045 | 0.582 | 156 |
XLP/PVC 18-8P-S | 18 | 8 | 7/.0152 | 0.03 | 0.06 | 0.733 | 255 |
XLP/PVC 18-12P-S | 18 | 12 | 7/.0152 | 0.03 | 0.06 | 0.902 | 383 |
XLP/PVC 18-24P-S | 18 | 24 | 7/.0152 | 0.03 | 0.08 | 1.198 | 665 |
XLP/PVC 18-36P-S | 18 | 36 | 7/.0152 | 0.03 | 0.08 | 1.36 | 909 |
XLP/PVC 16-1P-S | 16 | 1 | 7/.0192 | 0.03 | 0.045 | 0.338 | 56 |
XLP/PVC 16-2P-S | 16 | 2 | 7/.0192 | 0.03 | 0.045 | 0.548 | 184 |
XLP/PVC 16-4P-S | 16 | 4 | 7/.0192 | 0.03 | 0.06 | 0.632 | 218 |
XLP/PVC 16-8P-S | 16 | 8 | 7/.0192 | 0.03 | 0.06 | 0.8 | 328 |
XLP/PVC 16-12P-S | 16 | 12 | 7/.0192 | 0.03 | 0.08 | 0.988 | 496 |
XLP/PVC 16-16P-S | 16 | 16 | 7/.0192 | 0.03 | 0.08 | 1.108 | 625 |
XLP/PVC 16-24P-S | 16 | 24 | 7/.0192 | 0.03 | 0.08 | 1.312 | 869 |
XLP/PVC 16-36P-S | 16 | 36 | 7/.0192 | 0.03 | 0.08 | 1.53 | 1258 |
SPOS Tray Cable (XLP/PVC)
-40°C to 90°C Instrumentation Cable
SPOS Tray Cable (XLP/PVC) Construction:
- Conductors: 18 AWG – 16 AWG Class B stranded bare copper per ASTM B-33 and B-8
- Insulation: Flame-retardant Cross-linked polyethylene (XLP)
- Color-Code: Black/White; Alpha/numeric print
- Shield: Individual and overall 100% coverage, aluminum/polyester foil shield
- Jacket: Black sunlight and moisture resistant Polyvinyl Chloride (PVC)
XLP/PVC SPOS Tray Cable Features:
- Rated 90°C wet or dry
- Sunlight and weather resistant
- Superior low temperature cold bend characteristics
- Excellent abrasion and chemical resistance
- Flame resistant jacket burns to ash and limited thermoplastic drip
SPOS Tray Cable (XLP/PVC) Applications:
- Approved for Class 1 Division 2 hazardous location per NEC Article 501 (TC)
- Designed for use in conduit, cable tray, or direct burial
- Developed for use in industrial and utility applications
SPOS Tray Cable (XLP/PVC) Approvals:
- UL 1277 Type TC, UL 1581, and UL 1685 approved
- ICEA S-73-532 and ICEA S-95-658 (WC70) rated
- Passes IEEE 383 Flame Test (70,000 btu)
- EPA 40 CFR, Part 261, Subpart C, heavy metals per Table 1, TCLP method
Part Number | AWG Size | No. of Pairs | Conductor Stranding | Nom. Insul. Thick. (in) | Nom. O.D. of Cable (in) | Approx LBS/MFT |
XLP/PVC 18-2P-SPOS | 18 | 2 | 7/.0152 | 0.03 | 0.49 | 98 |
XLP/PVC 18-4P-SPOS | 18 | 4 | 7/.0152 | 0.03 | 0.598 | 176 |
XLP/PVC 18-8P-SPOS | 18 | 8 | 7/.0152 | 0.03 | 0.755 | 290 |
XLP/PVC 18-12P-SPOS | 18 | 12 | 7/.0152 | 0.03 | 0.93 | 438 |
XLP/PVC 18-24P-SPOS | 18 | 24 | 7/.0152 | 0.03 | 1.254 | 796 |
XLP/PVC 18-36P-SPOS | 18 | 36 | 7/.0152 | 0.03 | 1.442 | 968 |
XLP/PVC 16-2P-SPOS | 16 | 2 | 7/.0192 | 0.03 | 0.562 | 140 |
XLP/PVC 16-4P-SPOS | 16 | 4 | 7/.0192 | 0.03 | 0.674 | 227 |
XLP/PVC 16-8P-SPOS | 16 | 8 | 7/.0192 | 0.03 | 0.8 | 375 |
XLP/PVC 16-12P-SPOS | 16 | 12 | 7/.0192 | 0.03 | 1.015 | 571 |
XLP/PVC 16-24P-SPOS | 16 | 24 | 7/.0192 | 0.03 | 1.368 | 1044 |
XLP/PVC 16-36P-SPOS | 16 | 36 | 7/.0192 | 0.03 | 1.574 | 1477 |